Type 1 surge protector for PV installation 500Vdc
Item No: FV25B/2-500 PV S
-DC surge protector specially used for photovoltaic system.
-The core parts are metal oxide vristor components with high discharge capacity.
-With Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
- Type 1/ Class B
- PV system voltage 500Vdc
-The core parts are metal oxide vristor components with high discharge capacity.
-With Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
- Type 1/ Class B
- PV system voltage 500Vdc
Product Description
1. Coding system example

2. Dimension and circuit diagram of surge arrester FV25B/2-500PVS

3.Electrical parameters of surge arrester FV25B/2-500PVS
4. Installation
(1).jpg)

2. Dimension and circuit diagram of surge arrester FV25B/2-500PVS

3.Electrical parameters of surge arrester FV25B/2-500PVS
Test class according to IEC61643-11:2011
|
I
|
||
Nominal Voltage
|
UN
|
500V DC
|
|
Max.continuous d.c. voltage[(L+/L-)->PE]/ [L+->L-]
|
Uc pv
|
530V DC
|
|
Maximum discharge current (8/20μs)
|
Imax
|
100kA
|
|
Nominal discharge current (8/20μs)
|
In
|
50kA
|
|
Impulse current (10/350μs)
|
Iimp
|
25kA
|
|
Voltage protective levelat In
|
Up
|
≤2.4kV
|
|
Isolation resistance
|
Risol
|
>102MΩ
|
|
Response time
|
tA
|
≤25ns
|
|
I/O Connections
|
By screw terminal:10-35mm2
By connection bus
|
||
Mounting
|
Symmetrical rail(EN50022/DIN46277-3)
|
||
Operation temperature range
|
-40℃~+85℃
|
||
Degree of protection
|
IP20
|
||
Housing material
|
UL94V0
|
||
Disconnection indicator
|
Mechanical indicator
|
||
Remote control contact
|
Yes
|
||
Color
|
Gray
|
||
Isolation resistance
|
By screw terminal:10-35mm2
By connection bus
|
||
Response time
|
Symmetrical rail(EN50022/DIN46277-3)
|
4. Installation
(1).jpg)