Loading Images

surge arrester Imax 80kA, 3P+N, 3 phase

Item No: FV40C/3+NPE-xxx S
-Class II / Type 2 surge arrester.
-Consisting of a base part and 3 MOV + 1GDT plug-in protection modules.
-For using in the lightning protection zones concept at boundary 1-2.
-The core parts are metal oxide vristor components with high discharge capacity.
-Low residual voltage and quick response
-Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
-Protection mode: L1, L2, L3-N, N-PE.

Product Description

1.Coding system


2.Dimension and circuit of surge arrester FV40C/3+NPE-xxx S

3.Electrical parameters of surge arrester FV40C/3+NPE-xxx S
Model No. FV40C/3+NPE-
150S
FV40C/3+NPE-
275S
FV40C/3+NPE-
320S
FV40C/3+NPE-
385S
FV40C/3+NPE-
440S
Rated Voltage UN VAC 110/220 230/400 230/400 230/400 230/400
Max. continuous. operating voltage L-N
UC VAC 150 275 320 385 440
Max. continuous. operating voltage N-PE
UC VAC 255 255 255 255 255
Nominal discharge current(8/20μs) In kA 40 40 40 40 40
Max. discharge current (8/20μs) Imax kA 80 80 80 80 80
Voltage protection level (at In) Up kV ≤1.0 ≤1.7 ≤2.0 ≤2.5 ≤2.7
Response time tA ns <25 <25 <25 <25 <25
Recommended back-up fuse A 125 125 125 125 125
Protection mode L/N-PE
I/O Connections By screw terminal:10-35mm2; By connection bus
Mounting Symmetrical rail(EN50022/DIN46277-3)
Operation temperature range -40℃~+85℃
Degree of protection IP20
Housing material UL94V0
Disconnection indicator Mechanical indicator (Green: OK, Red: Replace)
Remote control contact Optional


Inquire