Loading Images

Dc surge protection, 3 poles 1000Vdc type 1+2 for photovoltaic system

Item No: FV30B+C/3-1000 PV

-DC surge protective devicespecially used for photovoltaic system less than 1000Vdc.
-The core parts are metal oxide varistor components with high discharge capacity.
-With Reliable control thanks to Thermo Dynamic Control disconnector.
-Without remote signaling contact for control device.
-Fault indication via red mark in the inspection window.

Product Description

1. Coding system


2. Dimension and Circuit of type 1+2 1000Vdc surge protective device


3. Type 1+2 1000Vdc surge protective device electrical parameters

Model. No.

FV30B+C/3-1000PV

SPD protection conforms to EN50539-11/IEC61643-31

Type 1+2

SPD installation type conforms to EN50539-11/IEC61643-31

ClassI+II

Protection level conforms to DIN VDE0675-6

B+C

Type of Network

Photovoltaic systemsDC side

Protectionmode

(+/-)-PE , (-/+)-PE

Nominal Voltage UN

1000 Vdc

Maximum continuous operating voltage for PV application UCPV

1200 Vdc

Continuous operating current ICPV

<20 µA

Residual current IPE

20 µA dc

500 µA ac

Standby power consumption PC

25 mVA

Maximum discharge current (8/20μs) Imax

50 kA

Nominal discharge current (8/20μs) In

25 kA

Impuse discharge current (10/350μs) Iimp

5 kA

Voltage protection level Up

≤3.8 kV

Isolation resistance Risol

1000 MΩ

Response time tA

≤25 ns

Remote control contact

NO

Disconnection indicator

Mechanical indicator

(Green: OK, Red: Replace)

Minimum area of connecting cable

6 mm2

Maximum area of connecting cable

35 mm2

Installation location

Inside

Mounting type

35mm DIN rail acc. to EN 60715

Color

Gray

Degree of protection

IP20

Housing material

UL94V-0

Ambient temperature

-40°C ~+80°C

Altitude

2000 m (amsl (above mean sea level))

Permissible humidity

30%~90%



4.Type 1+2 1000Vdc surge protective device installation



Inquire